- FAQ > Low-voltage Power Distribution Products > Power Management Meters > Electrical Indicators
FAQ
Keyword Search
FAQ within [ Electrical Indicators ]
-
Support status for IEC61850 (ME96SS series).
This model does NOT comply with the IEC61850. More Details >>
- No:22147
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:11
-
Setting upon delivery (ME96SS series).
It is not available. All configuration shall be conducted by the customer. More Details >>
- No:22149
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:49
-
Installation compatibility with ME96NSR (ME96SS series).
They are the same dimensions. (Dimensions of an installation hole is 92 mm in length and width. Install this model two points with mounting brackets.) More Details >>
- No:22160
- Release Date:2018/08/27 16:41
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
-
Initialization the set values (ME96SS series).
It is possible to initialize set values depending on setting. The method of initializing the setting value differs depending on the model. More Details >>
- No:22166
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:21
-
Disable an alarm for motor starting current (ME96SS series).
This model has “Motor Starting Current Mask Function”. This function stops the alarm output and updating of the maximum values during the setting time when a... More Details >>
- No:22175
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:51
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
-
Wire length for analog output and contact output(ME96SS series)
It depends on the service conditions. Refer to the following guidelines. ① Contact output Contact output for ME96 series is no-voltage "a" contact. The... More Details >>
- No:24807
- Release Date:2019/03/27 12:12
-
Availability for battery exchange for Logging Unit (ME96SS series).
The battery of the Logging unit (ME-0000BU-SS96) is NOT exchangeable. Please order a new unit. More Details >>
- No:22152
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:54
21-30 of Total 57