The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
-
Availability for direct measurement of 400V loads (ME96SS series).
This model is available for direct measurement of 400V loads at the STAR connection in Three-phase 3-wire system. More Details >>
- No:22150
- Release Date:2018/08/27 16:41
-
Response speed of the analog output (ME96SS series).
The response speed of the analog output is 2 seconds or less. The response speed of harmonic measurement is 10 seconds or less. More Details >>
- No:22157
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:12
-
IP protection class (ME96SS series).
In a board installation state, the protection class is equivalent to IP50. This model is not waterproof. More Details >>
- No:22158
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:13
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
-
Power supply upon setting (ME96SS series).
It is necessary to supply an auxiliary power. As for an auxiliary power supply, you can use 50 Hz or 60 Hz from 100 VAC to 240 VAC and from 100 VDC to 240... More Details >>
- No:22161
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:14
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME9... More Details >>
- No:22162
- Release Date:2018/08/27 16:41
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22