Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
-
Compatibility between present model and new model for the CC-Link (ME96SS series).
The CC-Link is compatible with the new model. More Details >>
- No:22151
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:51
-
Availability for special primary current and special primary voltage (ME96SS series).
This model is able to be used under unusual primary current and unusual primary voltage as long as the user sets each value within the selectable range as ... More Details >>
- No:22148
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:15
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
-
Response speed of the analog output (ME96SS series).
The response speed of the analog output is 2 seconds or less. The response speed of harmonic measurement is 10 seconds or less. More Details >>
- No:22157
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:12
-
Wire length for analog output and contact output(ME96SS series)
It depends on the service conditions. Refer to the following guidelines. ① Contact output Contact output for ME96 series is no-voltage "a" contact. The... More Details >>
- No:24807
- Release Date:2019/03/27 12:12
-
LCD COM is flashing (ME96SS series).
A reason varies with the connection situation of options. (Please refer to the section 6 of the User’s Manual.) In case of MODBUS RTU Error content: ... More Details >>
- No:22186
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:20
-
Support status for IEC61850 (ME96SS series).
This model does NOT comply with the IEC61850. More Details >>
- No:22147
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:11