Measuring received energy and the transferred energy (ME96SS series).
It is possible to measure the received energy and the transferred energy separately. More Details >>
- No:22176
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:53
-
Checking non-displayed digit of active energy (ME96SS series).
Pressing buttons of the “+” and the “-” at the same time on the measurement screen for 2 seconds shifts the unit of active energy as follows. The measured ... More Details >>
- No:22172
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:44
-
With ME96SS ver.B, four measurement values can be checked digitally on one screen. For models before ME96SS ver.B, up to three measured values can be checked... More Details >>
- No:37806
- Release Date:2020/04/10 15:09
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
-
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
- No:37704
- Release Date:2020/01/29 18:36
-
Concurrent-use of MODBUS RTU and MODBUS TCP (ME96SS series).
MODBUS RTU communication and MODBUS TCP communication can be used at the same time. More Details >>
- No:22188
- Release Date:2018/08/27 16:41
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
-
Read data stored by the built-in logging function
The stored data can be read from MODBUS RTU communication. To use this function, MODBUS RTU communication is required. It is not available with MOD... More Details >>
- No:37808
- Release Date:2020/04/10 15:09
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41