The viewpoint of the instantaneous factor operating characteristics graph
It means multiples of the settling value. For example, when an instantaneous factor operation settling value of a relay is 30 A, 100% is read as 30 A. More Details >>
- No:23707
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. The high voltage receiving facility rule defines “The ... More Details >>
- No:23730
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
In steady state, it is 5.0 VA, and during operation, it is 6.0 VA. More Details >>
- No:23715
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Because the contact capacity is different to that of a contact for trip, it cannot be used for tripping. Refer to the catalog for the contact capacity. More Details >>
- No:23737
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
In CT circuit, it is 5 A. More Details >>
- No:23713
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
That is right. More Details >>
- No:23722
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG