Measurement value different from other measuring instrument (ME96SS series).
The current value of this instrument is different from the current value of the other measuring instrument (such as a clamp meter).
Answer
In general, in case of measurement by the average method, the waveform including harmonics cause large error.
This model uses the RMS value method and measures a right value despite including harmonics.
In case of using an instrument of average method, measuring value of this instrument may be different from the value of average method.
Please refer to the section 6 of the User’s Manual.
This model uses the RMS value method and measures a right value despite including harmonics.
In case of using an instrument of average method, measuring value of this instrument may be different from the value of average method.
Please refer to the section 6 of the User’s Manual.