FAQ


FAQAbout Products
FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
- No:22403
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Fixed-type and Adjustable-type of V-type Operating handle
For Fixed type, the depth from the circuit breaker mounting surface to the panel board front is fixed. Adjustable-type is used when the depth from the circui... More Details >>
- No:22433
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
About Low-voltage Power Distribution Products
Main circuit of US-H* type is used for only AC power supply. For DC powersupply, we provide US-KD8 type solid state contactor. More Details >>
- No:23339
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
AL/AX/SHT/UVT terminal markings and wire colors
The color of terminal identification tube and lead wire is same.For one AL switch, 98/ALa terminal : red, 96/ALb terminal : blue, 95/ALc terminal : grayFor S... More Details >>
- No:22396
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Shunt Trip for CP30-BA can be provided. However, the pole of that with Shunt Trip is "Relay type" without overcurrent tripping element. Internal circuit is "... More Details >>
- No:22423
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Equipment
-
About Low-voltage Power Distribution Products
A thermal load relay is intended for burnout protection of three-phasesquirrel cage motor. When direct current is applied to the thermal loadrelay, the opera... More Details >>
- No:23281
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
A circuit breaker must have interrupting ratings. These are classified as rated short-circuit breaking capacities in IEC 60947-2.e rated ultimate short-circu... More Details >>
- No:22341
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
281-290 of Total 322