ACB How to check the operating characteristic
Y-2005 type field test equipment (it is sold separately) enable to check the operating characteristic easily. The test is conducted by connecting the test te... More Details >>
- No:22429
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ACB How to store drawout handle
Set the handle holder to the right side of the drawout frame with the included screw and nut, and store the drawout handle. However, the circuit breaker with... More Details >>
- No:22437
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
About Low-voltage Power Distribution Products
It is IP20. More Details >>
- No:23327
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
- No:37704
- Release Date:2020/01/29 18:36
- Category: Electrical Indicators
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
- Category: Electrical Indicators
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is a standard equipment (automatic reset type) and 30ms of one-pulse is output at overload tripping. Hold-type circuit is necessary since the output time ... More Details >>
- No:22428
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers