It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>
- No:22402
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Branch connection for MODBUS RTU communication
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
- No:24808
- Release Date:2019/03/27 14:44
- Category: Electrical Indicators , Energy Measuring Units
-
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Fixed-type and Adjustable-type of V-type Operating handle
For Fixed type, the depth from the circuit breaker mounting surface to the panel board front is fixed. Adjustable-type is used when the depth from the circui... More Details >>
- No:22433
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
301-310 of Total 323