As to action upon memory shortage of the SD memory card.
It will stop outputting logging data from the Logging Unit. [SD C.] LED will be high-speed blinking (repeat of 0.25sec ON → 0.25sec OFF). Backup the data ... More Details >>
- No:22135
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Simultaneous data acquisition of MODBUS RTU communication and Optional Unit.
It is possible to simultaneously collect data by MODBUS RTU communication and Optional Unit connected. Provided that MODBUS RTU communication cannot collec... More Details >>
- No:22140
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Cause of "minus" indication for electric power value (EcoMonitorPlus/Light).
Following causes are assumed for the error. 1. Wrong orientation of the sensor? 2. 1-side and 3-side of the sensor are reversed? 3. Is connection betwe... More Details >>
- No:22143
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Basic Unit manufactured in October 2016 or before is version A, which has restrictions on usage. The connectable number of extension units is two, not three ... More Details >>
- No:38008
- Release Date:2020/11/12 13:02
- Category: Energy Measuring Units
-
Extension of current sensor cable (EcoMonitorPlus/Light).
Use an extension cable (Model: EMU2-CB-T1M / EMU2-CB-T5M/EMU2-CB-T10M / EMU2-CB-T1MS / EMU2-CB-T5MS / EMU2-CB-T10MS) for extending the cable between EcoMonit... More Details >>
- No:22118
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:47
- Category: Energy Measuring Units
-
As to changing location of the decimal point and units of the measured value.
Since location of the decimal point or units of the measured value displayed is decided by Total load power, it is impossible to change location of the decim... More Details >>
- No:22139
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Error No.001(EcoMonitorPlus, EcoMonitorLight)
Error "No. 001" means start failure of CC-Link communication unit. Please try either step. Solution: ・Press and hold the reset button of CC-Link communica... More Details >>
- No:24810
- Release Date:2019/03/27 14:44
- Category: Energy Measuring Units
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>
- No:38042
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units
-
Checking the disconnection or communications error status of the Energy measuring Unit
There is no way to detect a disconnection or communications error in the Energy measuring Unit. As an alternative idea, we have two solutions to monitor t... More Details >>
- No:38043
- Release Date:2021/02/25 17:54
- Category: Energy Saving Data Collecting Servers