FAQ


FAQAbout Products
FAQ
Keyword Search
Energy Saving Supporting Devices
FAQ within [ Energy Saving Supporting Devices ]
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>
- No:38042
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units
-
As to connecting an Extension Unit for an Insulation Monitor Model (Model: EMU4-LG1-MB).
Connectable. Provided that it is impossible to extend a measuring circuit for insulation monitoring. More Details >>
- No:22123
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to ejecting an SD memory card.
The timing for ejecting an SD memory card is specified as below table according to the state of the [SD C.] LED of the Logging Unit for the Energy Measuring ... More Details >>
- No:22121
- Release Date:2018/08/27 16:41
- Update:2018/09/07 13:04
- Category: Energy Measuring Units
-
Checking the IP address of EcoWebServerIII
(1) Open the front cover on the server section, and set the MODE switch to the "STOP" position. (2) Set the RESET switch to the "SEL." position. (3) After ... More Details >>
- No:38044
- Release Date:2021/02/25 17:54
- Category: Energy Saving Data Collecting Servers
-
Simultaneous data acquisition of MODBUS RTU communication and Optional Unit.
It is possible to simultaneously collect data by MODBUS RTU communication and Optional Unit connected. Provided that MODBUS RTU communication cannot collec... More Details >>
- No:22140
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
For file transfer period and file transfer time (EcoWebServerIII).
Files are transferred once an hour. Transfer time can be set from 10min / 20min / 30min / 40min / 50min. More Details >>
- No:22117
- Release Date:2018/08/27 16:41
- Category: Energy Saving Data Collecting Servers
-
Recommended replacement cycle for battery (EcoWebServerIII).
Recommended replacement cycle of the battery (Q6BAT) for the EcoWebServerIII (MES3-255C-EN, MES3-255C-DM-EN)is 3 years. Provided that battery life varies acc... More Details >>
- No:22113
- Release Date:2018/08/27 16:41
- Update:2018/08/31 15:45
- Category: Energy Saving Data Collecting Servers
-
Checking the disconnection or communications error status of the Energy measuring Unit
There is no way to detect a disconnection or communications error in the Energy measuring Unit. As an alternative idea, we have two solutions to monitor t... More Details >>
- No:38043
- Release Date:2021/02/25 17:54
- Category: Energy Saving Data Collecting Servers
-
Download of EcoWebServerIII graph data.
Currently displayed date graph is downloadable. Downloaded data is not changed only by changing the date. Change date, then press [Display] to update the g... More Details >>
- No:22116
- Release Date:2018/08/27 16:41
- Category: Energy Saving Data Collecting Servers
-
When displaying current value on EcoWebServerIII, the display goes blank.
Measuring error may have occurred. Please confirm in system log file on the web screen whether there are some errors occurred. If measuring error is detect... More Details >>
- No:22114
- Release Date:2018/08/27 16:41
- Category: Energy Saving Data Collecting Servers
11-20 of Total 47