Wire length for analog output and con...
It depends on the service conditions. Refer to the following guidelines. ① Contact output Contact output for ME96 series is no-voltage "a" contact. The... More Details >>
Turning off the LCD display and backl...
It is impossible to turn off the LCD. It is possible to turn off back lights. When any button is not pressed for 5 minutes, the automatic off mode setting... More Details >>
Simultaneous data acquisition of MODB...
It is possible to simultaneously collect data by MODBUS RTU communication and Optional Unit connected. Provided that MODBUS RTU communication cannot collec... More Details >>
LCD COM is flashing (ME96SS series).
A reason varies with the connection situation of options. (Please refer to the section 6 of the User’s Manual.) In case of MODBUS RTU Error content: ... More Details >>
Read data stored by the built-in logg...
The stored data can be read from MODBUS RTU communication. To use this function, MODBUS RTU communication is required. It is not available with MOD... More Details >>
Connectable number of MODBUS RTU (ME9...
It is connectable with up to 31 units. It is necessary to prepare at least 3 PCs for connecting with 64 units. (31 units + 31 units + 2 units) More Details >>
As to batch storing of data file (Eco...
Using the setting software attached with an EcoWebServerIII (MES3-255C-EN, MES3-255C-DM-EN), it is able to collectively store data per every kind. Addition... More Details >>
The power factor does not match the i...
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
Active energy (lower digit indication...
Regardless of setting, the value of the default digit length is replied. When the register address “1304” for 6-digit display is set, the value varies w... More Details >>
Replied value on the communication op...
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>