FAQ


FAQAbout Products
FAQ
Keyword Search
Energy Saving Supporting Devices
FAQ within [ Energy Saving Supporting Devices ]
-
As to action upon memory shortage of the SD memory card.
It will stop outputting logging data from the Logging Unit. [SD C.] LED will be high-speed blinking (repeat of 0.25sec ON → 0.25sec OFF). Backup the data ... More Details >>
- No:22135
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Extension of current sensor cable (EcoMonitorPlus/Light).
Use an extension cable (Model: EMU2-CB-T1M / EMU2-CB-T5M/EMU2-CB-T10M / EMU2-CB-T1MS / EMU2-CB-T5MS / EMU2-CB-T10MS) for extending the cable between EcoMonit... More Details >>
- No:22118
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:47
- Category: Energy Measuring Units
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers
-
A dedicated Display Unit (Model: EMU4-D65) is used to set the EcoMonitorPlus (Model :EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB, EMU4-A2, EMU4-VA2, EMU4-AX4, EMU... More Details >>
- No:22128
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to compensation for power failure (EcoMonitorPlus/Light).
Since the setting value, integrated value (electric energy (consumption, regeneration), reactive energy, periodic electric energy, pulse count and operating ... More Details >>
- No:22141
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to periodic electric energy (EcoMonitorPlus/Light).
It means an integrated electric energy (consumption) while an external input (contact input) is ON. It is a measurement element different from the electric... More Details >>
- No:22124
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Method for measuring a circuit over 600A (EcoMonitorPlus/Light).
Attach a current transformer (CT) whose secondary current is 5A to the measuring point, then connect a split-type 5A current sensor (Model: EMU-CT5-A, EMU2-C... More Details >>
- No:22119
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:38
- Category: Energy Measuring Units
-
Cause of "minus" indication for electric power value (EcoMonitorPlus/Light).
Following causes are assumed for the error. 1. Wrong orientation of the sensor? 2. 1-side and 3-side of the sensor are reversed? 3. Is connection betwe... More Details >>
- No:22143
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to logging period of the internal memory of the main unit.
Logging period of the internal memory of the main unit as following: 1. In case of detailed data Logging period differs according to logging cycle for deta... More Details >>
- No:22137
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:43
- Category: Energy Measuring Units
-
Checking the IP address of EcoWebServerIII
(1) Open the front cover on the server section, and set the MODE switch to the "STOP" position. (2) Set the RESET switch to the "SEL." position. (3) After ... More Details >>
- No:38044
- Release Date:2021/02/25 17:54
- Category: Energy Saving Data Collecting Servers
11-20 of Total 47