FAQ


FAQAbout Products

FAQ
Keyword Search
Energy Saving Supporting Devices
FAQ within [ Energy Saving Supporting Devices ]
-
As to connecting an Extension Unit for an Insulation Monitor Model (Model: EMU4-LG1-MB).
Connectable. Provided that it is impossible to extend a measuring circuit for insulation monitoring. More Details >>
- No:22123
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to compensation for power failure (EcoMonitorPlus/Light).
Since the setting value, integrated value (electric energy (consumption, regeneration), reactive energy, periodic electric energy, pulse count and operating ... More Details >>
- No:22141
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Cause of "minus" indication for electric power value (EcoMonitorPlus/Light).
Following causes are assumed for the error. 1. Wrong orientation of the sensor? 2. 1-side and 3-side of the sensor are reversed? 3. Is connection betwe... More Details >>
- No:22143
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Cautions for replacing a battery (Model: EMU4-LM).
Make sure to power OFF of the EcoMonitorLight or EcoMonitorPlus when replacing a battery of the Logging Unit (Model: EMU4-LM) for the Energy Measuring Unit. ... More Details >>
- No:22125
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to using SD memory card at multiple locations.
Setting different logging ID enables that one SD memory card can be used for several Logging Units. Settable logging ID is 1 to 255. More Details >>
- No:22132
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to changing location of the decimal point and units of the measured value.
Since location of the decimal point or units of the measured value displayed is decided by Total load power, it is impossible to change location of the decim... More Details >>
- No:22139
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Basic Unit manufactured in October 2016 or before is version A, which has restrictions on usage. The connectable number of extension units is two, not three ... More Details >>
- No:38008
- Release Date:2020/11/12 13:02
- Category: Energy Measuring Units
-
Display Unit (Model: EMU4-D65) manufactured in October 2016 or before is version A, S/W version: 1.05, which does not support either Pulse Input Unit (Model:... More Details >>
- No:38009
- Release Date:2020/11/12 13:03
- Category: Energy Measuring Units
-
Pulse magnification setting of EMU4-PX4(Pulse Input Unit)
Match the setting values with EMU4-PX4 and EcoWebServerIII. No need to consider one-cycle operation because it is automatically calculated in EcoWebServerII... More Details >>
- No:38041
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers
-
Method for creating a daily/monthly report using logging data (Model: EMU4-LM).
Using Logging Unit Utility (free software), it is able to create a daily/monthly report using logging data acquired by the Logging Unit for the Energy Measur... More Details >>
- No:22120
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
21-30 of Total 47