FAQ


FAQAbout Products
FAQ
Keyword Search
Energy Saving Supporting Devices
FAQ within [ Energy Saving Supporting Devices ]
-
Recommended replacement cycle for battery (EcoWebServerIII).
Recommended replacement cycle of the battery (Q6BAT) for the EcoWebServerIII (MES3-255C-EN, MES3-255C-DM-EN)is 3 years. Provided that battery life varies acc... More Details >>
- No:22113
- Release Date:2018/08/27 16:41
- Update:2018/08/31 15:45
- Category: Energy Saving Data Collecting Servers
-
Checking the disconnection or communications error status of the Energy measuring Unit
There is no way to detect a disconnection or communications error in the Energy measuring Unit. As an alternative idea, we have two solutions to monitor t... More Details >>
- No:38043
- Release Date:2021/02/25 17:54
- Category: Energy Saving Data Collecting Servers
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers
-
Branch connection for MODBUS RTU communication
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
- No:24808
- Release Date:2019/03/27 14:44
- Category: Electrical Indicators , Energy Measuring Units
-
Error No.001(EcoMonitorPlus, EcoMonitorLight)
Error "No. 001" means start failure of CC-Link communication unit. Please try either step. Solution: ・Press and hold the reset button of CC-Link communica... More Details >>
- No:24810
- Release Date:2019/03/27 14:44
- Category: Energy Measuring Units
-
Pulse magnification setting of EMU4-PX4(Pulse Input Unit)
Match the setting values with EMU4-PX4 and EcoWebServerIII. No need to consider one-cycle operation because it is automatically calculated in EcoWebServerII... More Details >>
- No:38041
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers
-
Setting of "Master / slave setting switch" (Model: EMU4-D65).
It is assumed that setting of "Master/Slave setting switch" at the bottom of the Display Unit (Model: EMU4-D65) for the Energy Measuring Unit is wrong. Perfo... More Details >>
- No:22126
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
41-47 of Total 47