Measurable minimum load (ME96SS series).
In case of the input current of less than 0.005 A, the measurement values are as follows: Current: 0 A, Power supply: 0 W, Reactive power: 0 var, Apparent... More Details >>
- No:22155
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:04
- Category: Electrical Indicators
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56
- Category: Electrical Indicators
-
With ME96SS ver.B, four measurement values can be checked digitally on one screen. For models before ME96SS ver.B, up to three measured values can be checked... More Details >>
- No:37806
- Release Date:2020/04/10 15:09
- Category: Electrical Indicators
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
- Category: Electrical Indicators
-
Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Setting upon delivery (ME96SS series).
It is not available. All configuration shall be conducted by the customer. More Details >>
- No:22149
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:49
- Category: Electrical Indicators
-
Read data stored by the built-in logging function
The stored data can be read from MODBUS RTU communication. To use this function, MODBUS RTU communication is required. It is not available with MOD... More Details >>
- No:37808
- Release Date:2020/04/10 15:09
- Category: Electrical Indicators