MEASURE LED lights while measuring electric power over 0.4% of the total load power. Check below points: 1. Is voltage wiring connected? 2. Are the trans... More Details >>
- No:22144
- Release Date:2018/08/27 16:41
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
-
The function calculates the value of each measurement element of voltage, power factor by inputting only current using setting value. This function is used... More Details >>
- No:22127
- Release Date:2018/08/27 16:41
-
As to logging period of the optional SD memory card (EMU4-SD2GB).
Logging period of the optional SD memory card (EMU4-SD2GB) is according to the logging cycle of detail data and the number of measuring circuits. * It is ... More Details >>
- No:22136
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:48
-
As to ejecting an SD memory card.
The timing for ejecting an SD memory card is specified as below table according to the state of the [SD C.] LED of the Logging Unit for the Energy Measuring ... More Details >>
- No:22121
- Release Date:2018/08/27 16:41
- Update:2018/09/07 13:04
-
Cause of "minus" indication for electric power value (EcoMonitorPlus/Light).
Following causes are assumed for the error. 1. Wrong orientation of the sensor? 2. 1-side and 3-side of the sensor are reversed? 3. Is connection betwe... More Details >>
- No:22143
- Release Date:2018/08/27 16:41
-
As to logging period of the internal memory of the main unit.
Logging period of the internal memory of the main unit as following: 1. In case of detailed data Logging period differs according to logging cycle for deta... More Details >>
- No:22137
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:43
-
As to compensation for power failure (EcoMonitorPlus/Light).
Since the setting value, integrated value (electric energy (consumption, regeneration), reactive energy, periodic electric energy, pulse count and operating ... More Details >>
- No:22141
- Release Date:2018/08/27 16:41
-
As to compensation for power failure of Logging Unit for the Energy Measuring Unit.
Since the setting value is stored into nonvolatile memory, it will not be lost. The clock, logging data and system log data are retained as long as a batter... More Details >>
- No:22138
- Release Date:2018/08/27 16:41
- Update:2018/09/07 13:07
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>
- No:38042