FAQ


FAQAbout Products
- FAQ > Energy Saving Supporting Devices > Energy Saving Supporting Devices > Energy Measuring Units
FAQ
Keyword Search
FAQ within [ Energy Measuring Units ]
-
As to indication of the measurement value of the electric energy (EcoMonitorPlus/Light).
It measures from 0kWh(MWh) after going round. Integer 4 digits : 9999.98→9999.99→0000.00→0000.01kWh(MWh) Integer 5 digits : 99999.8→99999.9→00000.0→0000... More Details >>
- No:22131
- Release Date:2018/08/27 16:41
-
The function calculates the value of each measurement element of voltage, power factor by inputting only current using setting value. This function is used... More Details >>
- No:22127
- Release Date:2018/08/27 16:41
-
As to periodic electric energy (EcoMonitorPlus/Light).
It means an integrated electric energy (consumption) while an external input (contact input) is ON. It is a measurement element different from the electric... More Details >>
- No:22124
- Release Date:2018/08/27 16:41
-
As to logging period of the optional SD memory card (EMU4-SD2GB).
Logging period of the optional SD memory card (EMU4-SD2GB) is according to the logging cycle of detail data and the number of measuring circuits. * It is ... More Details >>
- No:22136
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:48
-
Method for creating a daily/monthly report using logging data (Model: EMU4-LM).
Using Logging Unit Utility (free software), it is able to create a daily/monthly report using logging data acquired by the Logging Unit for the Energy Measur... More Details >>
- No:22120
- Release Date:2018/08/27 16:41
-
Extension of current sensor cable (EcoMonitorPlus/Light).
Use an extension cable (Model: EMU2-CB-T1M / EMU2-CB-T5M/EMU2-CB-T10M / EMU2-CB-T1MS / EMU2-CB-T5MS / EMU2-CB-T10MS) for extending the cable between EcoMonit... More Details >>
- No:22118
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:47
-
MEASURE LED not blink (EcoMonitorPlus).
MEASURE LED lights while measuring electric power over 0.4% of the total load power. Check below points: 1. Is voltage wiring connected? 2. Are the trans... More Details >>
- No:22144
- Release Date:2018/08/27 16:41
-
As to required number of Display Unit.
When reconnecting each unit, customer can use one unit for several purposes. Provided that if it is needed to display the measured value constantly, the numb... More Details >>
- No:22142
- Release Date:2018/08/27 16:41
-
As to timing for outputting data file into the SD memory card.
EMU4-LM outputs data file at following timing. 1. When inserting the SD memory card while operating. 2. When power is ON in a state of the SD memory ca... More Details >>
- No:22133
- Release Date:2018/08/27 16:41
-
As to using SD memory card at multiple locations.
Setting different logging ID enables that one SD memory card can be used for several Logging Units. Settable logging ID is 1 to 255. More Details >>
- No:22132
- Release Date:2018/08/27 16:41