As to connecting an Extension Unit for an Insulation Monitor Model (Model: EMU4-LG1-MB).
Connectable. Provided that it is impossible to extend a measuring circuit for insulation monitoring. More Details >>
- No:22123
- Release Date:2018/08/27 16:41
-
Extension of current sensor cable (EcoMonitorPlus/Light).
Use an extension cable (Model: EMU2-CB-T1M / EMU2-CB-T5M/EMU2-CB-T10M / EMU2-CB-T1MS / EMU2-CB-T5MS / EMU2-CB-T10MS) for extending the cable between EcoMonit... More Details >>
- No:22118
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:47
-
A dedicated Display Unit (Model: EMU4-D65) is used to set the EcoMonitorPlus (Model :EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB, EMU4-A2, EMU4-VA2, EMU4-AX4, EMU... More Details >>
- No:22128
- Release Date:2018/08/27 16:41
-
As to action upon memory shortage of the SD memory card.
It will stop outputting logging data from the Logging Unit. [SD C.] LED will be high-speed blinking (repeat of 0.25sec ON → 0.25sec OFF). Backup the data ... More Details >>
- No:22135
- Release Date:2018/08/27 16:41
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>
- No:38042
- Release Date:2021/02/25 17:54
-
MEASURE LED not blink (EcoMonitorPlus).
MEASURE LED lights while measuring electric power over 0.4% of the total load power. Check below points: 1. Is voltage wiring connected? 2. Are the trans... More Details >>
- No:22144
- Release Date:2018/08/27 16:41
-
Branch connection for MODBUS RTU communication
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
- No:24808
- Release Date:2019/03/27 14:44
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
-
Sample program for MODBUS RTU communication(EcoMonitorPlus/EcoMonitorLight)
Sample programs are described in Programming Manual. Please refer to MODBUS Interface specifications (LSPY-9025) and MODBUS Interface soecifications(LSPY-9... More Details >>
- No:24806
- Release Date:2019/03/27 12:12
-
Method for creating a daily/monthly report using logging data (Model: EMU4-LM).
Using Logging Unit Utility (free software), it is able to create a daily/monthly report using logging data acquired by the Logging Unit for the Energy Measur... More Details >>
- No:22120
- Release Date:2018/08/27 16:41