As to changing location of the decimal point and units of the measured value.
Since location of the decimal point or units of the measured value displayed is decided by Total load power, it is impossible to change location of the decim... More Details >>
- No:22139
- Release Date:2018/08/27 16:41
-
As to required number of Display Unit.
When reconnecting each unit, customer can use one unit for several purposes. Provided that if it is needed to display the measured value constantly, the numb... More Details >>
- No:22142
- Release Date:2018/08/27 16:41
-
Refer to the below table as to current sensor usable for EcoMonitorPlus (Model: EMU4-BM1-MB, EMU4-HM1-MB, EMU4-A2, EMU4-VA2). *2. It will conform to UL st... More Details >>
- No:22130
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:54
-
Simultaneous data acquisition of MODBUS RTU communication and Optional Unit.
It is possible to simultaneously collect data by MODBUS RTU communication and Optional Unit connected. Provided that MODBUS RTU communication cannot collec... More Details >>
- No:22140
- Release Date:2018/08/27 16:41
-
Sample program for CC-LINK communication (EcoMonitorPlus/EcoMonitorLight)
Sample programs are described in Programming Manual. Please refer to suitable programming manual depending on CC-Link version which you use. ・Energy Measur... More Details >>
- No:24803
- Release Date:2019/03/27 12:12
-
MEASURE LED not blink (EcoMonitorPlus).
MEASURE LED lights while measuring electric power over 0.4% of the total load power. Check below points: 1. Is voltage wiring connected? 2. Are the trans... More Details >>
- No:22144
- Release Date:2018/08/27 16:41
-
Extension of current sensor cable (EcoMonitorPlus/Light).
Use an extension cable (Model: EMU2-CB-T1M / EMU2-CB-T5M/EMU2-CB-T10M / EMU2-CB-T1MS / EMU2-CB-T5MS / EMU2-CB-T10MS) for extending the cable between EcoMonit... More Details >>
- No:22118
- Release Date:2018/08/27 16:41
- Update:2018/09/07 11:47
-
A dedicated Display Unit (Model: EMU4-D65) is used to set the EcoMonitorPlus (Model :EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB, EMU4-A2, EMU4-VA2, EMU4-AX4, EMU... More Details >>
- No:22128
- Release Date:2018/08/27 16:41
-
As to timing for outputting data file into the SD memory card.
EMU4-LM outputs data file at following timing. 1. When inserting the SD memory card while operating. 2. When power is ON in a state of the SD memory ca... More Details >>
- No:22133
- Release Date:2018/08/27 16:41
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>