Medium-voltage Power Distribution Products
FAQ within [ Medium-voltage Power Distribution Products ]
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. Other than MPD-3 type ZVT, it is similar to the distan... More Details >>
- No:23719
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
Combination with other companies' peripheral devices
It is impossible. In Standard JIS C 4609, warranty is covered for combination of peripheral devices and relays. Therefore, combination with other companies’ ... More Details >>
- No:23718
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
That is described as below. (1) By laying ZCTs for two feeders having different loads, detected by one earth fault directional relay. In this case, it i... More Details >>
- No:23724
- Release Date:2018/09/19 17:16
- Update:2018/09/20 14:23
- Category: Protection Relays - MELPRO-A Series , MDG
-
Direction of the current in the incident detection
It is possible. More Details >>
- No:23712
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. The high voltage receiving facility rule defines “The ... More Details >>
- No:23730
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
Confirmation method of the start-up value
Set the display selection switch on the front upper right of the relay to “Time limit pass.” When a relay detects near the operation value, “0” will be displ... More Details >>
- No:23716
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
It operates. More Details >>
- No:23739
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
In steady state, it is 5.0 VA, and during operation, it is 6.0 VA. More Details >>
- No:23715
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Because when an undervoltage is detected, b contact will be closed, if power supply (P1-P2) is lost, the contact is retained. More Details >>
- No:23735
- Release Date:2018/09/19 17:16
- Update:2018/09/20 14:58
- Category: Protection Relays - MELPRO-A Series , MUV
-
Because the contact capacity is different to that of a contact for trip, it cannot be used for tripping. Refer to the catalog for the contact capacity. More Details >>
- No:23737
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
11-20 of Total 36