FAQ


FAQAbout Products

FAQ
Keyword Search
Medium-voltage Power Distribution Products
FAQ within [ Medium-voltage Power Distribution Products ]
-
It operates on a root mean square value of a fundamental wave. More Details >>
- No:23710
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Operating time of undervoltage detection
It operates with a settled operation time. More Details >>
- No:23731
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
The viewpoint of the instantaneous factor operating characteristics graph
It means multiples of the settling value. For example, when an instantaneous factor operation settling value of a relay is 30 A, 100% is read as 30 A. More Details >>
- No:23707
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
This relay uses the input voltage at the VT secondary side (P1-P2) as the relay control power source. When a rated voltage is input, b contact side of the co... More Details >>
- No:23733
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
A momentary power interruption is not detectable. More Details >>
- No:23732
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
That is described as below. (1) By laying ZCTs for two feeders having different loads, detected by one earth fault directional relay. In this case, it i... More Details >>
- No:23724
- Release Date:2018/09/19 17:16
- Update:2018/09/20 14:23
- Category: Protection Relays - MELPRO-A Series , MDG
-
In steady state, it is 5.0 VA, and during operation, it is 6.0 VA. More Details >>
- No:23715
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
It operates. More Details >>
- No:23739
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. Other than MPD-3 type ZVT, it is similar to the distan... More Details >>
- No:23719
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
Because between memories, a value becomes unstable, reset the position to the correct position. More Details >>
- No:23738
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON