It is impossible. Because the type is to detect by ZCT in an ungrounded system, the sensitivity becomes very high. More Details >>
- No:23727
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
Input from the primary side by combining with a peripheral device (ZCT). In Standard JIS C 4601, performance warranty is covered for combination of periphera... More Details >>
- No:23728
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
A momentary power interruption is not detectable. More Details >>
- No:23732
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
This relay uses the input voltage at the VT secondary side (P1-P2) as the relay control power source. When a rated voltage is input, b contact side of the co... More Details >>
- No:23733
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
Because when an undervoltage is detected, b contact will be closed, if power supply (P1-P2) is lost, the contact is retained. More Details >>
- No:23735
- Release Date:2018/09/19 17:16
- Update:2018/09/20 14:58
- Category: Protection Relays - MELPRO-A Series , MUV
-
The contact recovers automatically. More Details >>
- No:23736
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
The operating time of the instantaneous factor operating characteristics
That is right. Standard JIS C 4602 defines it shall be 50ms or shorter when 200% of the settling value is input. More Details >>
- No:23706
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Overload tolerance of an over current relay is 200 A, 1 second. Adjust CT ratio and others not to input more than 200 A. More Details >>
- No:23711
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
In CT circuit, it is 5 A. More Details >>
- No:23713
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
In steady state, it is 5.0 VA, and during operation, it is 6.0 VA. More Details >>
- No:23715
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
11-20 of Total 36