- FAQ > Medium-voltage Power Distribution Products > Protection Relays
FAQ
Keyword Search
FAQ within [ Protection Relays ]
-
It recovers without retaining. More Details >>
- No:23723
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
Set the frequency to meet the frequency of the region. Incorrect frequency prevents correct detection. More Details >>
- No:23740
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
Direction of the current in the incident detection
It is possible. More Details >>
- No:23712
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
In steady state, it is 5.0 VA, and during operation, it is 6.0 VA. More Details >>
- No:23715
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
The application of the overcurrent relay
It is possible. Connect R-phase to the terminal for R-phase of the relay, and T-phase to the terminal for T-phase of the relay. And the direction of a curren... More Details >>
- No:23709
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Overload tolerance of an over current relay is 200 A, 1 second. Adjust CT ratio and others not to input more than 200 A. More Details >>
- No:23711
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
That is described as below. (1) By laying ZCTs for two feeders having different loads, detected by one earth fault directional relay. In this case, it i... More Details >>
- No:23724
- Release Date:2018/09/19 17:16
- Update:2018/09/20 14:23
- Category: Protection Relays - MELPRO-A Series , MDG
-
The operating time of the instantaneous factor operating characteristics
That is right. Standard JIS C 4602 defines it shall be 50ms or shorter when 200% of the settling value is input. More Details >>
- No:23706
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Confirmation method of the start-up value
Set the display selection switch on the front upper right of the relay to “Time limit pass.” When a relay detects near the operation value, “0” will be displ... More Details >>
- No:23716
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
The contact recovers automatically. More Details >>
- No:23717
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
21-30 of Total 36