FAQ within [ Protection Relays - MELPRO-A Series ]
-
The prohibition position sets the maximum settling value. With the definite time current, all prohibition positions set 6 A, and with the instantaneous curre... More Details >>
- No:23714
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Because this relay derives the control power from input of the CT secondary current, when the input current falls below about 0.5 A for 2-phase input or abou... More Details >>
- No:23708
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. The high voltage receiving facility rule defines “The ... More Details >>
- No:23730
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. The high voltage receiving facility rule defines “The ... More Details >>
- No:23720
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
It is impossible. Because the type is to detect by ZCT in an ungrounded system, the sensitivity becomes very high. More Details >>
- No:23727
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
It recovers without retaining. More Details >>
- No:23723
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
It is impossible. It is required to combine with MZT type ZCT dedicated for our products. More Details >>
- No:23729
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
That is described as below. (1) By laying ZCTs for two feeders having different loads, detected by one earth fault directional relay. In this case, it i... More Details >>
- No:23726
- Release Date:2018/09/19 17:16
- Update:2018/09/20 13:26
- Category: Protection Relays - MELPRO-A Series , MGR
-
Up to 5 units. To connect 6 or more units, use Vo extended terminals (M-N) of a relay connected from MPD-3 type. From this Vo extended terminals, additional ... More Details >>
- No:23725
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MDG
-
The contact recovers automatically. More Details >>
- No:23736
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV