FAQ within [ Protection Relays - MELPRO-A Series ]
-
Operating time of undervoltage detection
It operates with a settled operation time. More Details >>
- No:23731
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
The application of the overcurrent relay
It is possible. Connect R-phase to the terminal for R-phase of the relay, and T-phase to the terminal for T-phase of the relay. And the direction of a curren... More Details >>
- No:23709
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
The operating time of the instantaneous factor operating characteristics
That is right. Standard JIS C 4602 defines it shall be 50ms or shorter when 200% of the settling value is input. More Details >>
- No:23706
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Because the contact capacity is different to that of a contact for trip, it cannot be used for tripping. Refer to the catalog for the contact capacity. More Details >>
- No:23737
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
It is impossible. Because the type is to detect by ZCT in an ungrounded system, the sensitivity becomes very high. More Details >>
- No:23727
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR
-
The viewpoint of the instantaneous factor operating characteristics graph
It means multiples of the settling value. For example, when an instantaneous factor operation settling value of a relay is 30 A, 100% is read as 30 A. More Details >>
- No:23707
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MOC
-
Set the frequency to meet the frequency of the region. Incorrect frequency prevents correct detection. More Details >>
- No:23740
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
It operates. More Details >>
- No:23739
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , COMMON
-
Contact recovery delay after applying voltage
This relay has a capacitor to operate in case of the lost power or at the maximum settling of an operation time. Because this capacitor needs a time to be ch... More Details >>
- No:23734
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MUV
-
It is required that the resistance is lower than 5 ohm for a go and return length using sealed cables. The high voltage receiving facility rule defines “The ... More Details >>
- No:23730
- Release Date:2018/09/19 17:16
- Category: Protection Relays - MELPRO-A Series , MGR