Because this relay derives the control power from input of the CT secondary current, when the input current falls below about 0.5 A for 2-phase input or abou... More Details >>
- No:23708
- Release Date:2018/09/19 17:16
-
The viewpoint of the instantaneous factor operating characteristics graph
It means multiples of the settling value. For example, when an instantaneous factor operation settling value of a relay is 30 A, 100% is read as 30 A. More Details >>
- No:23707
- Release Date:2018/09/19 17:16
-
The viewpoint of the definite time factor characteristic graph
It means multiples of the settling value. For example, when a definite time factor operation settling value of a relay is 3 A, 1x is read as 3 A and 5x is re... More Details >>