MEASURE LED not blink (EcoMonitorPlus).
MEASURE LED lights while measuring electric power over 0.4% of the total load power. Check below points: 1. Is voltage wiring connected? 2. Are the trans... More Details >>
- No:22144
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Sample program for CC-LINK communication (EcoMonitorPlus/EcoMonitorLight)
Sample programs are described in Programming Manual. Please refer to suitable programming manual depending on CC-Link version which you use. ・Energy Measur... More Details >>
- No:24803
- Release Date:2019/03/27 12:12
- Category: Energy Measuring Units
-
When displaying current value on EcoWebServerIII, the display goes blank.
Measuring error may have occurred. Please confirm in system log file on the web screen whether there are some errors occurred. If measuring error is detect... More Details >>
- No:22114
- Release Date:2018/08/27 16:41
- Category: Energy Saving Data Collecting Servers
-
Cause of "minus" indication for electric power value (EcoMonitorPlus/Light).
Following causes are assumed for the error. 1. Wrong orientation of the sensor? 2. 1-side and 3-side of the sensor are reversed? 3. Is connection betwe... More Details >>
- No:22143
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
Display Unit (Model: EMU4-D65) manufactured in October 2016 or before is version A, S/W version: 1.05, which does not support either Pulse Input Unit (Model:... More Details >>
- No:38009
- Release Date:2020/11/12 13:03
- Category: Energy Measuring Units
-
As to indication of the measurement value of the electric energy (EcoMonitorPlus/Light).
It measures from 0kWh(MWh) after going round. Integer 4 digits : 9999.98→9999.99→0000.00→0000.01kWh(MWh) Integer 5 digits : 99999.8→99999.9→00000.0→0000... More Details >>
- No:22131
- Release Date:2018/08/27 16:41
- Category: Energy Measuring Units
-
As to logging period of the optional SD memory card (EMU4-SD2GB).
Logging period of the optional SD memory card (EMU4-SD2GB) is according to the logging cycle of detail data and the number of measuring circuits. * It is ... More Details >>
- No:22136
- Release Date:2018/08/27 16:41
- Update:2018/09/07 12:48
- Category: Energy Measuring Units
-
As to compensation for power failure of Logging Unit for the Energy Measuring Unit.
Since the setting value is stored into nonvolatile memory, it will not be lost. The clock, logging data and system log data are retained as long as a batter... More Details >>
- No:22138
- Release Date:2018/08/27 16:41
- Update:2018/09/07 13:07
- Category: Energy Measuring Units
-
Error No.001(EcoMonitorPlus, EcoMonitorLight)
Error "No. 001" means start failure of CC-Link communication unit. Please try either step. Solution: ・Press and hold the reset button of CC-Link communica... More Details >>
- No:24810
- Release Date:2019/03/27 14:44
- Category: Energy Measuring Units
-
Pulse magnification setting of EMU4-PX4(Pulse Input Unit)
Match the setting values with EMU4-PX4 and EcoWebServerIII. No need to consider one-cycle operation because it is automatically calculated in EcoWebServerII... More Details >>
- No:38041
- Release Date:2021/02/25 17:54
- Category: Energy Measuring Units , Energy Saving Data Collecting Servers