Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ Q17nDSCPU ]

1-10 of Total 19

prev 1 / 2page next
  • Speed change during operation

    Specify the target axes during operation, and execute the following speed change request instruction. (1) Motion SFC program Speed change request CHGV, CHGVS... More Details >>

    • No:23574
    • Release Date:2018/09/14 15:09
  • Acceleration/deceleration time change

    Yes, the time can be changed during operation by using the acceleration/deceleration time change function. Set the acceleration/deceleration time change para... More Details >>

    • No:23568
    • Release Date:2018/09/14 15:09
  • Deceleration stop

    Because the rapid stop deceleration time is larger than the deceleration time.Set the rapid stop deceleration time within the range of 1 to the deceleration ... More Details >>

    • No:23550
    • Release Date:2018/09/14 15:09
  • PCPU READY complete flag (SM500)

    The PCPU READY complete flag (SM500) turns ON when no error is detected in the fixed parameters, servo parameters, and limit switch output data, which are ch... More Details >>

    • No:23564
    • Release Date:2018/09/14 15:09
  • Battery error

    The following shows the devices for the battery errors. • [SM51] Battery low latch Turn ON when the voltage of battery reduces to less than 2.5[V]. Remains O... More Details >>

    • No:23558
    • Release Date:2018/09/14 15:09
  • Error 2035

    Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command is the permissible speed or high... More Details >>

    • No:23577
    • Release Date:2018/09/14 15:09
  • Virtual servomotor

    Check the following signals. • Start accept flag (M2001 to M2032) • Positioning start complete signal (M4000+20n (n: Axis No.-1)) More Details >>

    • No:23552
    • Release Date:2018/09/14 15:09
    • Update:2023/02/08 10:39
  • Minor error120

    Minor error 120 occurs in the following case:The zero pass signal (M2406+20n) is OFF when the re-movement to the home position is performed by proximity dog,... More Details >>

    • No:23559
    • Release Date:2018/09/14 15:09
  • Error 3012

    Error 3012 occurs when the multiple CPU setting of PLC CPU (CPU No.1) does not match that of Motion CPU. (1) Check if the multiple CPU setting of the Multipl... More Details >>

    • No:23563
    • Release Date:2018/09/14 15:09
  • Alarm 2149

    Alarm 2149 (Main circuit OFF warning) occurs when the servo system turns ON with no power supplied to the servo main circuit. Review the condition of servo O... More Details >>

    • No:23566
    • Release Date:2018/09/14 15:09

1-10 of Total 19

Inquiries