  • JOG speed

    Set "[Cd.17] JOG speed" before starting the operation.When changing the speed during the operation, change it to the new speed with the speed change function. More Details >>

    • No:23581
    • Release Date:2018/09/14 15:09
  • Motor rotation direction

    Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>

    • No:23587
    • Release Date:2018/09/14 15:09
  • Servo status

    Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>

    • No:23588
    • Release Date:2018/09/14 15:09
    • Update:2023/03/09 10:02
  • Speed limit value

    No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>

    • No:23595
    • Release Date:2018/09/14 15:09
  • Speed change during JOG operation

    Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>

    • No:23606
    • Release Date:2018/09/14 15:09
  • Torque limit value change

    The torque limit value can be changed regardless of JOG operation status.Set the new torque limit value with "[Cd.22] New torque value/forward new torque val... More Details >>

    • No:23609
    • Release Date:2018/09/14 15:09
  • BUSY signal

    The BUSY signal turns ON even when position control of movement amount "0" is executed.However, since the ON time is short, the ON status may not be detected... More Details >>

    • No:23612
    • Release Date:2018/09/14 15:09
  • Parameter initialization

    The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>

    • No:23602
    • Release Date:2018/09/14 15:09
  • Restart

    Set "[Cd.6] Restart command" to "1". More Details >>

    • No:23619
    • Release Date:2018/09/14 15:09
  • Home position address

    Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>