No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>
- No:23595
- Release Date:2018/09/14 15:09
-
Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>
- No:23586
- Release Date:2018/09/14 15:09
-
The BUSY signal turns ON even when position control of movement amount "0" is executed.However, since the ON time is short, the ON status may not be detected... More Details >>
- No:23612
- Release Date:2018/09/14 15:09
-
Set "[Cd.6] Restart command" to "1". More Details >>
- No:23619
- Release Date:2018/09/14 15:09
-
Set "[Cd.17] JOG speed" before starting the operation.When changing the speed during the operation, change it to the new speed with the speed change function. More Details >>
- No:23581
- Release Date:2018/09/14 15:09
-
Error 1205 (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction se... More Details >>
- No:23614
- Release Date:2018/09/14 15:09
-
The following shows the setting value details.• 1 to 600: Positioning data No.• 7000 to 7004: Block start designation• 9001: Machine home position return• 90... More Details >>
- No:23597
- Release Date:2018/09/14 15:09
-
Servo motor rotation direction
To reflect the change, set "[PA14] Rotation direction selection/travel direction selection" and cycle the servo amplifier or execute a home position return a... More Details >>
- No:23620
- Release Date:2018/09/14 15:09
-
The following shows the procedure for changing the current value to a new value.(1) Write the new current value to "[Cd. 9] New current value".(2) Write "900... More Details >>
- No:23585
- Release Date:2018/09/14 15:09
-
It depends on the servo error.Some can be cleared by "[Cd.5] Axis error reset" but the other cannot unless the servo amplifier's power is turned OFF.Refer to... More Details >>