  • Electronic gear

    Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>

    • No:23586
    • Release Date:2018/09/14 15:09
  • Current value change

    The following shows the procedure for changing the current value to a new value.(1) Write the new current value to "[Cd. 9] New current value".(2) Write "900... More Details >>

    • No:23585
    • Release Date:2018/09/14 15:09
  • Servo status

    Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>

    • No:23588
    • Release Date:2018/09/14 15:09
    • Update:2023/03/09 10:02
  • Warning

    No, execute "[Cd.5] Axis error reset" to cancel the error after eliminating the error cause. More Details >>

    • No:23580
    • Release Date:2018/09/14 15:09
  • Degree axis

    Yes. (1) Absolute system (a) When the software stroke limit is invalid Positioning is carried out in a designated direction by "[Cd.40] ABS direction in deg... More Details >>

    • No:23601
    • Release Date:2018/09/14 15:09
  • HPR request flag

    It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>

    • No:23617
    • Release Date:2018/09/14 15:09
  • Inching operation

    Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>

    • No:23590
    • Release Date:2018/09/14 15:09
  • Positioning start

    There are two ways to start a positioning operation: (1) Set the "[Cd.3] Positioning start No.", and turn ON the positioning start signal. (2) Use the dedica... More Details >>

    • No:23593
    • Release Date:2018/09/14 15:09
  • Parameter initialization

    The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>

    • No:23602
    • Release Date:2018/09/14 15:09
  • Command in-position

    Refer to "b2: Command in-position flag" of "[Md.31] Status". More Details >>

    • No:23598
    • Release Date:2018/09/14 15:09