Compliance with SEMI-F47 for L series power supply module
How do I comply with SEMI-F47 when using the L series power supply module?
- Category :
Answer
Use the following power supply module with an input power of 200 VAC for compliance with SEMI-F47.
- Power supply module: L61P
With an input power of 100 VAC, supply power via an uninterruptible power supply (UPS) to the programmable controller system for compliance with SEMI-F47. Use an online UPS with voltage distortion of 5% or less.
(1) Connectable online Mitsubishi UPS products
- FREQUPS-V series
(2) Connectable Mitsubishi UPS products other than online types
- FREQUPS-A series
- FREQUPS-F series (serial number P or later)
- Power supply module: L61P
With an input power of 100 VAC, supply power via an uninterruptible power supply (UPS) to the programmable controller system for compliance with SEMI-F47. Use an online UPS with voltage distortion of 5% or less.
(1) Connectable online Mitsubishi UPS products
- FREQUPS-V series
(2) Connectable Mitsubishi UPS products other than online types
- FREQUPS-A series
- FREQUPS-F series (serial number P or later)
- Product Name
- MELSEC-L Series
- Series
- Power Supply
May I have your opinion?
Related FAQ
- Simultaneous broadcast reception setting for built-in Ethernet port LCPU
- Versions of built-in Ethernet port LCPU compatible with SNTP function
- Loop disconnection detection function and heater disconnection detection function of temperature control module
- Open setting of LCPU
- Versions of LCPU compatible with LJ71E71-100