FAQ within [ MELSEC-Q Series ]
-
Usage of PIDCONT instruction in process CPU
No. More Details >>
- No:22536
- Release Date:2018/09/03 17:28
-
Replacing an AnS I/O module with a Q I/O module
Yes. More Details >>
- No:22717
- Release Date:2018/09/03 17:29
-
This occurs because software required to display the Help window is not installed as standard in Windows7. Download the Windows Help program (WinHlp32.exe) f... More Details >>
- No:22674
- Release Date:2018/09/03 17:29
-
Versions of the QJ71C24N modules compatible with QnUDVCPU
The QJ71C24N series modules with serial numbers with upper 5 digits of "10042" or later indicate compatibility with QnUDVCPU. More Details >>
- No:22628
- Release Date:2018/09/03 17:29
-
Input derating is the percentage of simultaneous ON points, one of the specifications applied when input modules are used. When QX42 is used in a temperatur... More Details >>
- No:22692
- Release Date:2018/09/03 17:29
- Update:2018/10/03 16:23
-
Communication between Ethernet and FL-net
The communication between the Ethernet interface module and FL-net (OPCN-2) interface module cannot be established. More Details >>
- No:22683
- Release Date:2018/09/03 17:29
-
Cause of file register reset by latch clear operation in universal model QCPU
If Latch (1) is set in the device setting of PLC parameter, the contents of file registers are cleared by latch clear operation. Set Latch (2) to maintain t... More Details >>
- No:22584
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:31
-
Network No., Group No., and Station No. in Network Parameter
- Network No. is a number assigned to identify each network when multiple networks are configured. Each network No. must be unique. - Group No. is a num... More Details >>
- No:22550
- Release Date:2018/09/03 17:28
- Update:2018/09/20 15:48
-
Detecting the connection between a built-in Ethernet port QCPU and hub
You can check the connection to the hub with bit 10 of the special register SD1288. When bit 10 of the SD1288 is on, the QCPU is in connection with the hub. More Details >>
- No:22712
- Release Date:2018/09/03 17:29
-
We do not guarantee the operation of a system that involves cross cable connections. More Details >>
- No:22679
- Release Date:2018/09/03 17:29