Parameter settings required to use the MODBUS(R) interface module as a slave station
If preset initial values are used, parameters do not need setting.If changing the basic parameter or MODBUS(R) device assignment parameter, use a sequence pr... More Details >>
- No:22680
- Release Date:2018/09/03 17:29
-
QCPU built-in Ethernet port setting when using the simple PLC communication function
The following settings are required for the "Open Setting" for the number of connected external devices. - Protocol: "UDP" - Open System: "MELSOFT connecti... More Details >>
- No:22654
- Release Date:2018/09/03 17:29
- Update:2018/09/21 12:02
-
Operation error at the execution of a BIN instruction
Keep SM722 ON or correct the program so that any one of the ten numbers 0 to 9 is stored in each digit of the source data.An operation error occurs when data... More Details >>
- No:22635
- Release Date:2018/09/03 17:29
-
Settings of the built-in Ethernet port of the universal model QCPU
Make settings of the built-in Ethernet port in the [Built-in Ethernet Port Setting] tab of the PLC parameter in GX Works2 or GX Developer. More Details >>
- No:22618
- Release Date:2018/09/03 17:29
- Update:2018/09/21 10:06
-
Reading and writing bits/words using the FL-net (OPCN-2) interface module
The parameters and auto refresh settings for the FL-net (OPCN-2) interface module cannot be made using the Network Parameter items in GX Developer.Set those ... More Details >>
- No:22597
- Release Date:2018/09/03 17:29
-
Specification method of high-speed timer
To use a high-speed timer, insert a circuit of application instruction such as "OUTH T0 K100". More Details >>
- No:22549
- Release Date:2018/09/03 17:28
-
Change timing of the status of A/D conversion module's I/O signals
(1)If the A/D conversion enable signal is kept ON, conversion processing is kept performed. Once conversion processing is successfully performed, A/D conve... More Details >>
- No:22710
- Release Date:2018/09/03 17:29
- Update:2018/09/21 15:12
-
Input derating is the percentage of simultaneous ON points, one of the specifications applied when input modules are used. When QX42 is used in a temperatur... More Details >>
- No:22692
- Release Date:2018/09/03 17:29
- Update:2018/10/03 16:23
-
The numbers of POUs and steps of "Allocate Memory for 'Online Change'" in GX Works2
The maximum number of steps that an online change can process at a time is 512. More Details >>
- No:22672
- Release Date:2018/09/03 17:29
-
Deleting GX Developer when installing GX Works2
GX Developer does not need deleting when GX Works2 is installed. More Details >>