FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-Q Series
FAQ
Keyword Search
FAQ within [ MELSEC-Q Series ]
-
The error code "2401" is "FILE SET ERROR". The individual information parameter number "1100H" corresponds to a file register. The cause of the error is th... More Details >>
- No:22535
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:46
-
GX Developer's compatibility with 64-bit Windows 7
GX Developer Version 8.98C or later supports 64-bit Windows 7. To install GX Developer to a Windows 7-based personal computer, refer to the following techni... More Details >>
- No:22501
- Release Date:2018/09/03 17:28
- Update:2018/09/20 12:19
-
Insufficient memory capacity for sequence programs
It cannot be increased by installing an SRAM card. The size of executable program depends on the program memory size of the CPU. Use another CPU of which p... More Details >>
- No:22578
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:09
-
Follow the procedure below.(1)Eliminate the error cause.(2) Store the error code to be cleared in SD50.(3)Turn OFF and ON SM50.(4) The error is cleared. More Details >>
- No:22613
- Release Date:2018/09/03 17:29
-
File registers "R" use the block switching method. The number of file register points used are divided and specified in units of 32k points. When multiple ... More Details >>
- No:22512
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:29
-
GX Works2's USB driver installation procedure
The USB driver is not installed.The driver needs to be separately installed before the first connection to a CPU module. More Details >>
- No:22507
- Release Date:2018/09/03 17:28
-
Yes. A USB driver needs to be installed.For the installation procedure, refer to the following manual. - GX Developer Version 8 Operating Manual (Startup) More Details >>
- No:22504
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:10
-
The error code "2100" is "SP.UNIT LAY ERR.". This error may be caused by one of the following factors. (1) In the I/O assignment setting of the PLC parame... More Details >>
- No:22650
- Release Date:2018/09/03 17:29
- Update:2018/09/21 11:47
-
Error code "2200" in the universal model QCPU
The error code "2200" is "MISSING PARA.". The cause of the error is that a parameter file does not exist in all drives where parameters will be valid.As a re... More Details >>
- No:22614
- Release Date:2018/09/03 17:29
-
The error code "4100" is "OPERATION ERROR". The error occurs when a number is divided by 0 (Divisor D6268 value is 0). Make modifications so that the divis... More Details >>
- No:22533
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:43