FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-Q Series
FAQ
Keyword Search
FAQ within [ MELSEC-Q Series ]
-
Difference between FL-net interface modules QJ71FL71-T and QJ71FL71-T-F01
- QJ71FL71-T is a product which supports FL-net (OPCN-2) Version 1.00.- QJ71FL71-T-F01 is a product which supports FL-net (OPCN-2) Version 2.00.Since Version... More Details >>
- No:22551
- Release Date:2018/09/03 17:28
-
Returning to the overwrite mode in GX Developer
Press the INSERT key. More Details >>
- No:22599
- Release Date:2018/09/03 17:29
-
Whether or not totem pole output type encoders are connected
Totem pole output encoders cannot be connected to QD62.The following types of encoders can be connected.- Open collector output type encoders- CMOS level vol... More Details >>
- No:22641
- Release Date:2018/09/03 17:29
-
How to change the type of statement in GX Developer
Select [Search/Replace] -> [Replace statement/note type] from the menu and select "Change in PLC". More Details >>
- No:22647
- Release Date:2018/09/03 17:29
-
Difference between QH42P and QX41Y41P
The difference is I/O numbers used for input and output (XY). QH42P uses the same I/O numbers both for input and output. QX41Y41P uses sequential I/O numbers... More Details >>
- No:22539
- Release Date:2018/09/03 17:28
-
Battery replacement for universal model QCPU
The contents of the standard RAM and latch devices are not erased if the battery replacement is completed within three minutes, which is the backup power tim... More Details >>
- No:22558
- Release Date:2018/09/03 17:29
-
How to turn OFF the "COM.ERR" LED of the Ethernet module
The LED can be turned OFF by operations from GX Developer. The operation method is as follows.(1) Connect to the CPU in the standby system in Transfer Setup.... More Details >>
- No:22571
- Release Date:2018/09/03 17:29
-
It includes sample comments for special relay/special register and the intelligent function module. On the menu of GX Works2, select [Edit] -> [Import ... More Details >>
- No:22581
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:12
-
The numbers of POUs and steps of "Allocate Memory for 'Online Change'" in GX Works2
The maximum number of steps that an online change can process at a time is 512. More Details >>
- No:22672
- Release Date:2018/09/03 17:29
-
Setting of "Target MODBUS(R) device head number"
Set "(Last five digits of actual device number) - 1" for the Target MODBUS(R) device head number.Example) For the holding register 400018, set "17". More Details >>
- No:22682
- Release Date:2018/09/03 17:29
21-30 of Total 213