FAQ within [ MELSEC-Q Series ]
-
How to check automatically assigned devices in GX Works2
Click the local label to be checked and select "Cross Reference" from the right-click menu to check the devices. More Details >>
- No:22700
- Release Date:2018/09/03 17:29
-
Error code "2200" in the High-Performance model QCPU
The error code "2200" is "MISSING PARA.". It may be determined as the cause of the error that there is no parameter file in the parameter-valid drive that h... More Details >>
- No:22699
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:24
-
A/D conversions performed by Q64AD/Q68ADV/Q68ADI
(1) Sampling processing - Without the temperature drift compensation function Processing time = Number of channels usedx 80 (us/1 channel) - With the t... More Details >>
- No:22705
- Release Date:2018/09/03 17:29
- Update:2018/09/26 16:34
-
How to increase file register capacity
An SRAM card can increase file register capacity.1MB/2MB/4MB/8MB SRAM cards are available.The numbers of file registers that can be used with a 1MB, 2MB, 4MB... More Details >>
- No:22687
- Release Date:2018/09/03 17:29
-
Insufficient memory capacity for sequence programs
It cannot be increased by installing an SRAM card. The size of executable program depends on the program memory size of the CPU. Use another CPU of which p... More Details >>
- No:22578
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:09
-
Unable to select [Transfer Setup]
If a circuit is being monitored or a monitor window such as the device batch monitor window is open, [Transfer Setup] on the menu is grayed out. Select [Wi... More Details >>
- No:22548
- Release Date:2018/09/03 17:28
- Update:2018/09/20 15:40
-
How to copy comments from GX Developer to GX Works2
Launch GX Works2, select [Project] -> [Open Other Project], and read the data created with GX Developer. Copy the comment from the list of device comme... More Details >>
- No:22526
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:32
-
PLC type change in GX Developer
Follow the steps below and then execute PLC type change.- On the menu of GX Developer, select [Online] -> [Monitor] -> [Stop Monitoring (All Windows)],... More Details >>
- No:22522
- Release Date:2018/09/03 17:28
-
Difference between GX Works2 and GX Works
GX Works2 is programmable controller engineering software integrating programming and simulation of programmable controller and setting monitor tool functio... More Details >>
- No:22505
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:16
-
This occurs when the specified memory does not have consecutive free space in it. In this case, delete unnecessary files or arrange the PLC memory. Select ... More Details >>
- No:22604
- Release Date:2018/09/03 17:29
- Update:2018/09/20 18:03
21-30 of Total 213