FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-Q Series
FAQ
Keyword Search
FAQ within [ MELSEC-Q Series ]
-
Network No., Group No., and Station No. in Network Parameter
- Network No. is a number assigned to identify each network when multiple networks are configured. Each network No. must be unique. - Group No. is a num... More Details >>
- No:22550
- Release Date:2018/09/03 17:28
- Update:2018/09/20 15:48
-
How to set file register setting
No setting is required.File registers are enabled by default in basic model QCPU. More Details >>
- No:22555
- Release Date:2018/09/03 17:29
-
CF cards supported by the high speed data logger module
For applicable CF cards, refer to the latest version of the following manual.- High Speed Data Logger Module User's Manual- SH-080818ENG- 2.3 Connection Syst... More Details >>
- No:22607
- Release Date:2018/09/03 17:29
-
GX Works2's compatibility with Monitor (write mode)
From version 1.62Q, GX Works2 supports Monitor (write mode). Pressing Shift+F4 allows an online change. More Details >>
- No:22612
- Release Date:2018/09/03 17:29
- Update:2018/09/20 18:18
-
USB cable type for CPU modules
It is type B. More Details >>
- No:22622
- Release Date:2018/09/03 17:29
-
CPU modules that support the File Register Extended Setting
The universal model QCPU modules other than Q00UJCPU support the File Register Extended Setting. More Details >>
- No:22627
- Release Date:2018/09/03 17:29
-
Difference between Q24DHCCPU-V and Q12DCCPU-V
Hardware specifications are different. For hardware specifications, refer to the following manuals. - MELSEC-Q C Controller Module User's Manual - C Contro... More Details >>
- No:22629
- Release Date:2018/09/03 17:29
- Update:2018/09/21 10:41
-
Cost of runtime licenses for VxWorks
The cost is included in the price of C Controller modules. Extra payment is not required. More Details >>
- No:22653
- Release Date:2018/09/03 17:29
-
Setting of "Target MODBUS(R) device head number"
Set "(Last five digits of actual device number) - 1" for the Target MODBUS(R) device head number.Example) For the holding register 400018, set "17". More Details >>
- No:22682
- Release Date:2018/09/03 17:29
-
Whether or not device indirect specifications in structured ladder programs are allowed
Indirect specifications with "@" cannot be used in structured ladder programs and the Structured Text. Use indirect specifications in a ladder language program. More Details >>
- No:22697
- Release Date:2018/09/03 17:29
61-70 of Total 213