FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-Q Series
FAQ
Keyword Search
FAQ within [ MELSEC-Q Series ]
-
Compatibility with 64-bit Windows 7
GX Works2 Version 1.62Q or later supports Windows 7. More Details >>
- No:22554
- Release Date:2018/09/03 17:28
-
Operation error at the execution of a BIN instruction
Keep SM722 ON or correct the program so that any one of the ten numbers 0 to 9 is stored in each digit of the source data.An operation error occurs when data... More Details >>
- No:22635
- Release Date:2018/09/03 17:29
-
Specifying steps in printing data displayed in the window in GX Works2
GX Works2 Version 1.45X or later supports a print range specifying capability.Set "Start Step" and "End Step" for "Specified Print Range" in the Print window. More Details >>
- No:22695
- Release Date:2018/09/03 17:29
-
The corresponding operation depends on the counter type selected. (1) If "Linear Counter" is selected If the present counter value exceeds the upper limi... More Details >>
- No:22624
- Release Date:2018/09/03 17:29
- Update:2018/09/21 10:32
-
Change timing of the status of A/D conversion module's I/O signals
(1)If the A/D conversion enable signal is kept ON, conversion processing is kept performed. Once conversion processing is successfully performed, A/D conve... More Details >>
- No:22710
- Release Date:2018/09/03 17:29
- Update:2018/09/21 15:12
-
Boot operation from the standard ROM
The boot operation from the standard ROM is not possible.The program memory of universal model QCPU is a flash ROM.Thus, writing in the program memory achiev... More Details >>
- No:22553
- Release Date:2018/09/03 17:28
-
Open setting of the built-in Ethernet port QCPU
No.It is necessary to configure one port to use the MELSOFT connection. More Details >>
- No:22648
- Release Date:2018/09/03 17:29
-
How to check automatically assigned devices in GX Works2
Click the local label to be checked and select "Cross Reference" from the right-click menu to check the devices. More Details >>
- No:22700
- Release Date:2018/09/03 17:29
-
Set as follows in the Transfer Setup window. - Select "USB" for "PC side I/F". - Select "GOT" for "PLC side I/F" and select "via GOT (direct coupled) tra... More Details >>
- No:22598
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:55
-
Cables connected to the Ethernet port on the universal model QCPU
If a direct connection is made, either type can be used.If making a connection via a hub, use a straight cable. More Details >>
- No:22690
- Release Date:2018/09/03 17:29
1-10 of Total 213