- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
Refer to the following manual. MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals) Appendix 1 More Details >>
- No:22798
- Release Date:2018/09/03 17:30
-
Retention of auto tuning setting value for temperature control module
Use the automatic backup setting. While "1: enabled" is set in the CH[] automatic backup setting after auto tuning of PID constants in the buffer memory (Un\... More Details >>
- No:22795
- Release Date:2018/09/03 17:30
-
The conversion speed is as follows. - High speed: 20 microseconds per channel- Medium speed: 80 microseconds per channel- Low speed: 1 millisecond per channel More Details >>
- No:22776
- Release Date:2018/09/03 17:30
-
The heater disconnection detection function monitors the heater current on the transistor output. If no current flows when the transistor is ON, it is consi... More Details >>
- No:22773
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:58
-
Execution of the SOCRMODE instruction in the same connection during socket communication of LCPU
It can be executed for the same connection number. When data exist in the socket communication receive data area and the SOCRMODE instruction is executed, va... More Details >>
- No:22771
- Release Date:2018/09/03 17:30
-
Update timing of LD75 current feed value and machine feed value
The values are updated at the timing described below. - Current feed value: 0.9 ms - Machine feed value: 0.9 ms More Details >>
- No:22748
- Release Date:2018/09/03 17:29
-
LCPU built-in Ethernet port setting when using the simple PLC communication function
The following settings are required for the "Open Setting" for the number of connected external devices.- Protocol: "UDP"- Open System: "MELSOFT connection" More Details >>
- No:22739
- Release Date:2018/09/03 17:29
-
How to use L series extension modules
The extension module is used to configure the extension block when 10 modules or more are mounted to LCPU. Connect the branch module and the extension module... More Details >>
- No:22738
- Release Date:2018/09/03 17:29
-
Boot operation from the standard ROM
The boot operation from the standard ROM is not possible. The program memory of LCPU is a flash ROM. Thus, writing in the program memory achieves a ROM opera... More Details >>
- No:22728
- Release Date:2018/09/03 17:29
-
File switching timing of L series logging function
No. More Details >>
- No:22809
- Release Date:2018/09/03 17:30
91-100 of Total 105