FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
QnA-compatible 3E frame command for built-in Ethernet port in LCPU
The built-in Ethernet port in the L series CPU is not compatible with a multiple-block batch read command (0406) of the MC protocol. Executable commands are ... More Details >>
- No:22726
- Release Date:2018/09/03 17:29
-
Use of commercial SD memory cards
Yes. A commercial SD memory card can be used. (32 GB max.)Connectable SD memory cards that passed our operation check are listed in the technical bulletin. More Details >>
- No:22801
- Release Date:2018/09/03 17:30
-
LCPU internal clock synchronization
Use the time setting function to synchronize the internal clock. More Details >>
- No:22755
- Release Date:2018/09/03 17:30
-
Use of END cover with the branch module and extension module
Use an END cover applicable to the following. - The L6EC whose serial number (first six digits) is "*****2" or later- END cover with ERR terminal (optional i... More Details >>
- No:22815
- Release Date:2018/09/03 17:30
-
Versions of built-in Ethernet port LCPU compatible with SNTP function
The initial version and subsequent versions of L series CPU support the SNTP function. More Details >>
- No:22769
- Release Date:2018/09/03 17:30
-
Simultaneous use of simple PLC communication function and socket communication
The socket communication can be used simultaneously with the simple PLC communication function. More Details >>
- No:22740
- Release Date:2018/09/03 17:29
-
A password can be set. - Use the file password 32 function.- Number of characters: 4 to 32 (alphanumeric and special characters, case-sensitive)- Disabled op... More Details >>
- No:22810
- Release Date:2018/09/03 17:30
-
Execution of the SOCRMODE instruction in the same connection during socket communication of LCPU
It can be executed for the same connection number. When data exist in the socket communication receive data area and the SOCRMODE instruction is executed, va... More Details >>
- No:22771
- Release Date:2018/09/03 17:30
-
SNTP communication error in built-in Ethernet port LCPU
The error does not affect the CPU time. The CPU time is not set when a communication error occurs. More Details >>
- No:22783
- Release Date:2018/09/03 17:30
-
Cable length to connect to built-in Ethernet port in LCPU
The maximum length between a hub and a node is 100 m. The max. length connectable to a hub is 200m.When repeater hubs are used in cascade connection, the max... More Details >>
- No:22781
- Release Date:2018/09/03 17:30
11-20 of Total 105