FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
The data logging file transfer function allows for transfer of the logging data to an upper server regularly. It is transferred when data logging is switched... More Details >>
- No:22741
- Release Date:2018/09/03 17:29
-
Connection status detection between a hub and the built-in Ethernet port of LCPU
The bit 10 of the special register SD1288 provides the connection status to a hub. When the bit 10 of SD1288 is ON, a hub is connected. More Details >>
- No:22759
- Release Date:2018/09/03 17:30
-
Compliance with SEMI-F47 for L series power supply module
Use the following power supply module with an input power of 200 VAC for compliance with SEMI-F47. - Power supply module: L61PWith an input power of 100 VAC,... More Details >>
- No:22768
- Release Date:2018/09/03 17:30
-
The heater disconnection detection function monitors the heater current on the transistor output. If no current flows when the transistor is ON, it is consi... More Details >>
- No:22773
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:58
-
Simple PLC communication function
This function allows data communications between specified devices at the specified timing, using the built-in Ethernet. Device data such as production data ... More Details >>
- No:22737
- Release Date:2018/09/03 17:29
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
-
The error code "2200" is "MISSING PARA.". The causes of the error are described below. (1) The necessary parameter file does not exist in all drives. (2) ... More Details >>
- No:22749
- Release Date:2018/09/03 17:29
- Update:2018/09/22 09:12
-
The conversion speed is 20 microseconds per channel. More Details >>
- No:22826
- Release Date:2018/09/03 17:30
-
NTP support by the SNTP function of LCPU with built-in Ethernet port
NTP and SNTP are compatible. Therefore, an NTP server can be used for clock setting. More Details >>
- No:22744
- Release Date:2018/09/03 17:29
-
GX Developer Version 8.89T or later is supported.There are restrictions in some functions. For the details, refer to "Precautions on L Series Modules" in ... More Details >>
- No:22792
- Release Date:2018/09/03 17:30
- Update:2018/10/03 16:26
11-20 of Total 105