- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
-
SD1286 of LCPU with built-in Ethernet port
The bits 0 to F of the special register SD1286 (Receive state signal) correspond to the connection numbers 1 to 16. When it receives data, the corresponding ... More Details >>
- No:22786
- Release Date:2018/09/03 17:30
-
The error code "2200" is "MISSING PARA.". The causes of the error are described below. (1) The necessary parameter file does not exist in all drives. (2) ... More Details >>
- No:22749
- Release Date:2018/09/03 17:29
- Update:2018/09/22 09:12
-
Simultaneous use of auto logging and backup functions
The auto logging function and backup function cannot be used simultaneously. The backup function must be used after the logging function is stopped. (A singl... More Details >>
- No:22819
- Release Date:2018/09/03 17:30
-
Use of a commercial SD memory card in L series logging function
Yes. Recommended products are listed in the technical bulletin FA-A-0078. More Details >>
- No:22753
- Release Date:2018/09/03 17:29
- Update:2018/10/03 16:25
-
Precautions for use of SD memory card
Yes. Note that SD memory cards are formatted at the factory. If an SD memory card needs to be reformatted, format it using the CPU module. More Details >>
- No:22779
- Release Date:2018/09/03 17:30
-
CPU clock setting by SNTP functions via built-in Ethernet port in LCPU
The clock setting of the CPU module is set automatically in accordance with the clock data collected from the time information server (SNTP server) on the LAN. More Details >>
- No:22736
- Release Date:2018/09/03 17:29
-
The error code "2401" is "FILE SET ERROR". The individual information parameter number "1100H" corresponds to a file register. The cause of the error is that... More Details >>
- No:22797
- Release Date:2018/09/03 17:30
-
Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
-
Sampling cycle of L60TCTT4(BW) and L60TCRT4(BW)
It is selectable from the following. - 500 ms/4 channels (Default)- 250 ms/4 channels More Details >>
- No:22824
- Release Date:2018/09/03 17:30