FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
Remedy to an error message when performing online change in LCPU
After data is written to the program cache memory (SRAM), it is automatically transferred to the program memory (flash ROM). Therefore, additional online cha... More Details >>
- No:22763
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:50
-
Use of 4E frame for built-in Ethernet port of LCPU
The built-in Ethernet port in the L series is compatible only with the QnA-compatible 3E frame. The 4E frame is not supported. More Details >>
- No:22761
- Release Date:2018/09/03 17:30
-
- Ambient temperature: 25+/-5degrees Celsius Full scalex (+/-0.3%) - Ambient temperature: 0 to 55degrees Celsius Full scalex (+/-0.7%) More Details >>
- No:22823
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:35
-
Index modification when using extended data register in LCPU
It is not possible to specify index modification to cross over the boundary between the internal user device (D) and the extended data register (D). Change t... More Details >>
- No:22822
- Release Date:2018/09/03 17:30
-
Indication accuracy - Ambient temperature: 25+/-5 degrees Celsius Full scale x (+/-0.3%) - Ambient temperature: 0 to 55degrees Celsius Full scale x (+/-0... More Details >>
- No:22820
- Release Date:2018/09/03 17:30
- Update:2018/09/26 16:51
-
Number of data sampling points in LCPU logging function
Up to 1280 points. (128 points per setting, and up to 10 data logging settings) More Details >>
- No:22805
- Release Date:2018/09/03 17:30
-
The minimum input response times are different. The minimum input response time is 100 microseconds for standard inputs, and 10 microseconds for high-speed i... More Details >>
- No:22804
- Release Date:2018/09/03 17:30
-
GX Developer Version 8.89T or later is supported.There are restrictions in some functions. For the details, refer to "Precautions on L Series Modules" in ... More Details >>
- No:22792
- Release Date:2018/09/03 17:30
- Update:2018/10/03 16:26
-
Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
-
Simultaneous broadcast transmission setting for built-in Ethernet port LCPU
To send simultaneous broadcast using UDP, set the parameters as follows.- Destination IP Address: FF.FF.FF.FFh - Destination Port Number: Other than FFFFh (S... More Details >>
- No:22785
- Release Date:2018/09/03 17:30
51-60 of Total 105