FAQ within [ MELSEC-L Series ]
-
TCP retransmission timer setting for built-in Ethernet port LCPU
For the built-in Ethernet port in the L series CPU, the TCP retransmission timer setting is fixed and unchangeable. The retransmission occurs six times. The... More Details >>
- No:22745
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:52
-
How to use PWM output of LCPU built-in I/O
Set the PWM output-on-width and the PWM output cycle, and then execute a dedicated instruction "ICPWM instruction". More Details >>
- No:22757
- Release Date:2018/09/03 17:30
-
Execution of the SOCRMODE instruction in the same connection during socket communication of LCPU
It can be executed for the same connection number. When data exist in the socket communication receive data area and the SOCRMODE instruction is executed, va... More Details >>
- No:22771
- Release Date:2018/09/03 17:30
-
Simultaneous broadcast reception setting for built-in Ethernet port LCPU
To receive simultaneous broadcast using UDP, set the parameters as follows. - Destination IP Address: FF.FF.FF.FFh - Destination Port No.: Other than FFFFh (... More Details >>
- No:22772
- Release Date:2018/09/03 17:30
-
Use of an A-compatible 1E frame for the built-in Ethernet port of LCPU
The built-in Ethernet port in the L series is compatible only with a QnA-compatible 3E frame of the MC protocol. An A-compatible 1E frame is not supported. More Details >>
- No:22731
- Release Date:2018/09/03 17:29
-
Operation during power failure
It stops during execution. More Details >>
- No:22764
- Release Date:2018/09/03 17:30
-
Use of commercial SD memory cards
Yes. A commercial SD memory card can be used. (32 GB max.)Connectable SD memory cards that passed our operation check are listed in the technical bulletin. More Details >>
- No:22801
- Release Date:2018/09/03 17:30
-
The contents of the standard RAM and latch devices are not erased if the battery replacement is completed within three minutes, which is the backup power tim... More Details >>
- No:22733
- Release Date:2018/09/03 17:29
-
Use of 4E frame for built-in Ethernet port of LCPU
The built-in Ethernet port in the L series is compatible only with the QnA-compatible 3E frame. The 4E frame is not supported. More Details >>
- No:22761
- Release Date:2018/09/03 17:30
-
FNC connector pin layout in L series I/O module and Q series I/O module
Yes. They have the same pin layout. More Details >>
- No:22774