FAQ within [ MELSEC-L Series ]
-
Method to prevent the BAT.LED from turning on
To prevent an LED from turning on when an error occurs, set 0 to the relevant factor number setting area (4 bits for each) in SD207 to SD209. To disable the ... More Details >>
- No:22754
- Release Date:2018/09/03 17:29
-
Use of 4E frame for built-in Ethernet port of LCPU
The built-in Ethernet port in the L series is compatible only with the QnA-compatible 3E frame. The 4E frame is not supported. More Details >>
- No:22761
- Release Date:2018/09/03 17:30
-
Use of END cover with the branch module and extension module
Use an END cover applicable to the following. - The L6EC whose serial number (first six digits) is "*****2" or later- END cover with ERR terminal (optional i... More Details >>
- No:22815
- Release Date:2018/09/03 17:30
-
Behavior of sequence program in event of momentary power failure in LCPU
(1) When it happened no longer than the allowable momentary power failure time. The module records an error log and suspends the operation processing. Ho... More Details >>
- No:22756
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:43
-
Simultaneous broadcast reception setting for built-in Ethernet port LCPU
To receive simultaneous broadcast using UDP, set the parameters as follows. - Destination IP Address: FF.FF.FF.FFh - Destination Port No.: Other than FFFFh (... More Details >>
- No:22772
- Release Date:2018/09/03 17:30
-
Use SP.FWRITE instruction to save the data to an SD memory card in CSV format. More Details >>
- No:22727
- Release Date:2018/09/03 17:29
-
Simple PLC communication function
This function allows data communications between specified devices at the specified timing, using the built-in Ethernet. Device data such as production data ... More Details >>
- No:22737
- Release Date:2018/09/03 17:29
-
NTP support by the SNTP function of LCPU with built-in Ethernet port
NTP and SNTP are compatible. Therefore, an NTP server can be used for clock setting. More Details >>
- No:22744
- Release Date:2018/09/03 17:29
-
PLC write not possible due to memory overload
If comments cannot be stored in the program memory, write them in the standard ROM or a memory card. Calculate the memory capacity in GX Works2 or GX Develop... More Details >>
- No:22767
- Release Date:2018/09/03 17:30
-
The conversion speed is as follows. - High speed: 20 microseconds per channel- Medium speed: 80 microseconds per channel- Low speed: 1 millisecond per channel More Details >>
- No:22776
- Release Date:2018/09/03 17:30