Yes.When connecting a GOT, set the mode setting switch of AJ65BT-R2N to "5" (MELSOFT connection mode). More Details >>
- No:23047
- Release Date:2018/09/03 17:31
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>
- No:23044
- Release Date:2018/09/03 17:31
-
How to make the expanded cyclic setting for CC-Link local stations
Make the expanded cyclic setting for a CC-Link local station using the programming tool, GX Developer or GX Works2. Follow the procedure below. (1) Set th... More Details >>
- No:23030
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:17
-
Using a FROM/TO instruction after AJ71UC24 is replaced with QJ71C24N
I/O signals and buffer memory addresses need to be changed but data communications can be conducted using a FROM/TO instruction and X/Y signals. More Details >>
- No:23017
- Release Date:2018/09/03 17:31
-
Terminating resistors for RS-485 communication of LJ71C24
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22999
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:25
-
Mixing line topologies with star topologies in the CC-Link IE Field Network
Line topologies and star topologies can be mixed. More Details >>
- No:23059
- Release Date:2018/09/03 17:31
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
-
T-branch connection and star topology for CC-Link networks
- T-branch T-branch is a connection type that branches one line from a main line. To establish a T-branch CC-Link network, use the repeater module AJ65S... More Details >>
- No:23024
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:00
-
Detecting the number of disconnections when using QJ71E71-100
The number of disconnections detected can be checked by reading the buffer memory address 5203H (Disconnection detection count). Disconnections are detected ... More Details >>
- No:23003
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:49
-
The CC-Link remote I/O modules' model names represents as follows:- AJ65SBTB1 - S: Compact type - B1: 1-wire terminal block, 1-common type- AJ65SBTB2 - S:... More Details >>