Use a T-branch repeater module instead of a terminal block. More Details >>
- No:23086
- Release Date:2018/09/03 17:31
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>
- No:23044
- Release Date:2018/09/03 17:31
-
Using a FROM/TO instruction after AJ71UC24 is replaced with QJ71C24N
I/O signals and buffer memory addresses need to be changed but data communications can be conducted using a FROM/TO instruction and X/Y signals. More Details >>
- No:23017
- Release Date:2018/09/03 17:31
-
Ethernet cables for the CC-Link IE Field Network
General-purpose Ethernet cables that meet the 1000BASE-T standard (category 5e or higher) can be used. We recommend double shielded cables. Recommended pro... More Details >>
- No:22989
- Release Date:2018/09/03 17:31
- Update:2019/06/27 15:47
-
Intelligent Buffer Select of the CC-Link parameter
Set the size of buffer memory used for transient transmission (by dedicated instructions) to local stations, the standby master station, and intelligent devi... More Details >>
- No:22977
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-16DT1 and AJ65SBTB1-16DT2
Major differences are shown below. - AJ65SBTB1-16DT1 - Rated input current approx. 5 mA - ON voltage/ON current 15 VDC or higher/3.0 mA or higher - O... More Details >>
- No:22972
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:04
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
-
Applicable size for plug-in connector socket block on QJ71C24N-R4
Use the plate terminal packaged with the module. The size of the plate terminal is 1.0 mm wide with a thickness of 0.8 mm. More Details >>
- No:23043
- Release Date:2018/09/03 17:31
-
Detecting the number of disconnections when using QJ71E71-100
The number of disconnections detected can be checked by reading the buffer memory address 5203H (Disconnection detection count). Disconnections are detected ... More Details >>
- No:23003
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:49
-
Yes. More Details >>