FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > Network related products
FAQ
Keyword Search
FAQ within [ Network related products ]
-
Data length for fixed buffer data communications by QJ71E71
The units of send data and receive data are shown below. - Fixed buffer data communications with the "Procedure Exist" control method: Words - Fixed buff... More Details >>
- No:23061
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:17
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
-
Relation between CC-Link terminals and signal lines
The following shows the relations between CC-Link terminals and signal lines. - DA : Blue -DB: White -DG: Yellow More Details >>
- No:23077
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:11
-
Differences between CC-Link IE Control Network and CC-Link IE Field Network
The CC-Link IE Control Network is a high-capacity controller network whose maximum number of link points is 128k words. The CC-Link IE Field Network is an al... More Details >>
- No:23085
- Release Date:2018/09/03 17:31
-
Resistor value for CC-Link cables
The value depends on the type of cable in use. - Ver.1.10-compatible CC-Link dedicated cables: 110 ohm, 1/2W - CC-Link dedicated cables (Version 1.00): 110... More Details >>
- No:22983
- Release Date:2018/09/03 17:31
- Update:2018/10/03 14:42
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
-
Difference between networks called CC-Link and those called MELSEC
CC-Link IE, supported by the CC-Link Partner Association, is an open field network standard that integrates networks, from a controller network to field/moti... More Details >>
- No:23013
- Release Date:2018/09/03 17:31
-
Remedies for WDT errors on a MELSECNET/H board
The error code indicates a WDT (watchdog timer) error. It is determined as the cause that the MELSECNET/H driver cannot work due to a computer or OS hang, or... More Details >>
- No:22969
- Release Date:2018/09/03 17:31
-
"[ ]" in the CC-Link remote I/O modules' model name "AJ65[ ]BT" represents as follows: - None: Standard type - S: Compact type - F: Low profile waterpro... More Details >>
- No:22974
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:12