Identify disconnected stations using either of the following methods. (1) Select [Diagnostics] -> [CC-Link Diagnostics].from the menu in GX Works2 or G... More Details >>
- No:23053
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:59
-
Link register assignments in MELSECNET/10 networks
For any type of MELSECNET network (II, /10, and H), B and W devices with the same number cannot be used for multiple stations as write areas. Following th... More Details >>
- No:22971
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:24
-
Remedies for WDT errors on a MELSECNET/H board
The error code indicates a WDT (watchdog timer) error. It is determined as the cause that the MELSECNET/H driver cannot work due to a computer or OS hang, or... More Details >>
- No:22969
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-32DTE1 and AJ65SBTB1-32DT1
Major differences are shown below. - AJ65SBTB1-32DT1 - Input type positive common (sink type) - Rated input current approx. 5 mA - ON voltage/ON curr... More Details >>
- No:23022
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:52
-
CC-Link slave station's flashing L.ERR LED
If the L.ERR LED flashes at irregular intervals, it may indicate that no terminating resistor has been connected or the communication is instable due to the ... More Details >>
- No:23001
- Release Date:2018/09/03 17:31
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
-
Read and write operations for CC-Link buffer memory
There is no problem in writing/reading data into/from the buffer memory using a FROM/TO instruction with the refresh device setting left blank.The refresh de... More Details >>
- No:23015
- Release Date:2018/09/03 17:31
-
Difference between the CC-Link IE Controller Network and a MELSECNET/H network
The CC-Link IE Controller Network is an improved system that has a higher processing speed and a larger data capacity than the MELSECNET/H network system (PL... More Details >>
- No:22979
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:17
-
Using Ethernet UTP cables for the CC-Link IE Controller
Ethernet UTP cables cannot be used. More Details >>
- No:23062
- Release Date:2018/09/03 17:31
-
Difference between networks called CC-Link and those called MELSEC
CC-Link IE, supported by the CC-Link Partner Association, is an open field network standard that integrates networks, from a controller network to field/moti... More Details >>
- No:23013
- Release Date:2018/09/03 17:31