- FAQ > Controllers > Programmable Controllers MELSEC > Network related products
FAQ
Keyword Search
FAQ within [ Network related products ]
-
Intelligent Buffer Select of the CC-Link parameter
Set the size of buffer memory used for transient transmission (by dedicated instructions) to local stations, the standby master station, and intelligent devi... More Details >>
- No:22977
- Release Date:2018/09/03 17:31
-
Precautions taken when QJ61BT11 is replaced with QJ61BT11N
Set the Network Parameter as shown below. (1) If QJ61BT11 is in the remote net mode, use the remote net Ver.1 mode for QJ61BT11N. (2) If QJ61BT11 is in the... More Details >>
- No:22967
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:20
-
Link data from communication error stations in a CC-Link network
The remote input RX of the master station and the remote input RX and remote output RY of local stations clear/hold the data from an error station according ... More Details >>
- No:23057
- Release Date:2018/09/03 17:31
-
Precaution about MELSECNET/H connection (2)
- Set the network module mounted in system A to station number 0 (multiplexed remote master station). Set the network module mounted in system B to any sta... More Details >>
- No:23054
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:00
-
Station number settings for MELSECNET/H networks
A station number can be skipped by setting the station as a reserved station. More Details >>
- No:23045
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-16DT and AJ65SBTB1-16DT1
Major differences in input specifications are shown below. - AJ65SBTB1-16DT - Rated input current approx. 7 mA - ON voltage/ON current 14 VDC or higher/... More Details >>
- No:23035
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:24
-
Assigning X and Y signals of AJ65SBTB1-32DT
X and Y assignments are as follows.- X0 to XF- Y10 to Y1F More Details >>
- No:23034
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31