Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>
- No:23009
- Release Date:2018/09/03 17:31
-
Precautions taken when QJ61BT11 is replaced with QJ61BT11N
Set the Network Parameter as shown below. (1) If QJ61BT11 is in the remote net mode, use the remote net Ver.1 mode for QJ61BT11N. (2) If QJ61BT11 is in the... More Details >>
- No:22967
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:20
-
Station number settings for MELSECNET/H networks
A station number can be skipped by setting the station as a reserved station. More Details >>
- No:23045
- Release Date:2018/09/03 17:31
-
Buffer memory addresses of CC-Link modules
If the remote net Ver.1 mode is used, each station number is given fixed buffer memory addresses.If the remote net Ver.2 mode is used, different buffer memor... More Details >>
- No:22992
- Release Date:2018/09/03 17:31
-
Applicable size for plug-in connector socket block on QJ71C24N-R4
Use the plate terminal packaged with the module. The size of the plate terminal is 1.0 mm wide with a thickness of 0.8 mm. More Details >>
- No:23043
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Detecting the number of disconnections when using QJ71E71-100
The number of disconnections detected can be checked by reading the buffer memory address 5203H (Disconnection detection count). Disconnections are detected ... More Details >>
- No:23003
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:49
-
Settings required for transient transmission
The routing parameter settings are required for transient transmission to the CPU module with another network No. The request source station, relay station,... More Details >>
- No:22995
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:40
-
Difference in specifications between CC-Link versions
Ver.1.10 is a standard where CC-Link station-to-station cable length restriction in Ver. 1.00 has been removed, and the length of all station-to-station cabl... More Details >>
- No:22975
- Release Date:2018/09/03 17:31
-
SB/SW refresh device setting with CC-Link
SB/SW uses 512 points of refresh devices. More Details >>
- No:23081
- Release Date:2018/09/03 17:31