FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > Network related products
FAQ
Keyword Search
FAQ within [ Network related products ]
-
CC-Link signals checked when an error occurs
Check the following signals.- Module error signal : X0- Host data link status signal: X1- Other station data link status signal: X3 More Details >>
- No:23021
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Whether or not multiple QJ72LP25-25 modules can be mounted
No, only a single QJ72LP25-25 can be mounted (and is to be mounted on the CPU slot on a main base unit). More Details >>
- No:23042
- Release Date:2018/09/03 17:31
-
Applicable size for plug-in connector socket block on QJ71C24N-R4
Use the plate terminal packaged with the module. The size of the plate terminal is 1.0 mm wide with a thickness of 0.8 mm. More Details >>
- No:23043
- Release Date:2018/09/03 17:31
-
Unit of receive data used by the QJ71C24N series pre-defined protocol support function
The fixed data is used for specific codes and character strings such as a command. Setting a device is not required. More Details >>
- No:23049
- Release Date:2018/09/03 17:31
-
Continuous executions of protocols by the QJ71C24N series CPRTCL instruction
One CPRTCL instruction can execute a maximum of eight protocols. More Details >>
- No:23050
- Release Date:2018/09/03 17:31
-
Model name of the connector used for the FCN connector type CC-Link remote I/O module
FCN connectors (40-pin connector) are shown below.- A6CON1 (soldering connector)- A6CON2 (crimp connector)- A6CON3 (pressure-displacement connector)- A6CON4 ... More Details >>
- No:23056
- Release Date:2018/09/03 17:31
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
-
The functional grounding is applied to ensure the reliability of the communication. More Details >>
- No:23076
- Release Date:2018/09/03 17:31
-
Terminating resistors for RS-422 communication of QJ71C24N
The resistance value is 330 ohm, 1/4 W. More Details >>
- No:22965
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:33
31-40 of Total 110