- FAQ > Controllers > Programmable Controllers MELSEC > Network related products
FAQ
Keyword Search
FAQ within [ Network related products ]
-
About network parameters when building MELSECNET/10 with Q02HCPU-A
Q02(H)CPU-A is the AnUCPU equivalent. When establishing a MELSECNET/10 network, set the refresh parameter with which SB/SW data is transferred to "Y/D" or o... More Details >>
- No:23005
- Release Date:2018/09/03 17:31
- Update:2018/09/26 14:42
-
Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>
- No:23009
- Release Date:2018/09/03 17:31
-
Read and write operations for CC-Link buffer memory
There is no problem in writing/reading data into/from the buffer memory using a FROM/TO instruction with the refresh device setting left blank.The refresh de... More Details >>
- No:23015
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-32DTE1 and AJ65SBTB1-32DT1
Major differences are shown below. - AJ65SBTB1-32DT1 - Input type positive common (sink type) - Rated input current approx. 5 mA - ON voltage/ON curr... More Details >>
- No:23022
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:52
-
CC-Link IE Controller cable standard
Use the cables that meet the IEC60793-2-10 Types A1a.1 optical fiber standard. The connectors are LC (duplex) connectors. Two cores are required.The core di... More Details >>
- No:23032
- Release Date:2018/09/03 17:31
- Update:2018/09/27 12:14
-
Difference between AJ65SBTB1-16DT and AJ65SBTB1-16DT1
Major differences in input specifications are shown below. - AJ65SBTB1-16DT - Rated input current approx. 7 mA - ON voltage/ON current 14 VDC or higher/... More Details >>
- No:23035
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:24
-
Communication between CPU modules established by QJ71E71
The communication between QJ71E71 series modules can be established if READ/WRITE instructions are used. More Details >>
- No:23036
- Release Date:2018/09/03 17:31
-
Receiving data when no receive complete code is designated (QJ71C24N)
Data are received on a received data count basis. If there is no receive complete code and variable length data is received, the data is received at every no... More Details >>
- No:23038
- Release Date:2018/09/03 17:31
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
-
Whether or not multiple QJ72LP25-25 modules can be mounted
No, only a single QJ72LP25-25 can be mounted (and is to be mounted on the CPU slot on a main base unit). More Details >>
- No:23042
- Release Date:2018/09/03 17:31