Link register assignments in MELSECNET/10 networks
For any type of MELSECNET network (II, /10, and H), B and W devices with the same number cannot be used for multiple stations as write areas. Following th... More Details >>
- No:22971
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:24
-
Whether or not MC protocol frames can be used after A1SJ71UC24 is replaced with QJ71C24N
The QJ71C24N series modules can be accessed using A-compatible 1C frames, but the following restrictions are imposed. The access is limited to the devices wi... More Details >>
- No:22970
- Release Date:2018/09/03 17:31
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
-
CC-Link IE Controller cable standard
Use the cables that meet the IEC60793-2-10 Types A1a.1 optical fiber standard. The connectors are LC (duplex) connectors. Two cores are required.The core di... More Details >>
- No:23032
- Release Date:2018/09/03 17:31
- Update:2018/09/27 12:14
-
What makes the ERR LED flash in a CC-Link network
A link error has occurred in one of the slave stations in connection.Master station: Check the parameter again.Slave station: Reassess the power supply, the ... More Details >>
- No:23023
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-32DT and AJ65SBTB1-32DT2
Major differences are shown below. - AJ65SBTB1-32DT- Leakage current at OFF 0.25 mA or lower- Protection function (overload protection, overvoltage protectio... More Details >>
- No:22985
- Release Date:2018/09/03 17:31
-
Difference in specifications between CC-Link versions
Ver.1.10 is a standard where CC-Link station-to-station cable length restriction in Ver. 1.00 has been removed, and the length of all station-to-station cabl... More Details >>
- No:22975
- Release Date:2018/09/03 17:31
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
-
How to make the expanded cyclic setting for CC-Link local stations
Make the expanded cyclic setting for a CC-Link local station using the programming tool, GX Developer or GX Works2. Follow the procedure below. (1) Set th... More Details >>
- No:23030
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:17
-
Read and write operations for CC-Link buffer memory
There is no problem in writing/reading data into/from the buffer memory using a FROM/TO instruction with the refresh device setting left blank.The refresh de... More Details >>
- No:23015
- Release Date:2018/09/03 17:31